Expert Technical Evaluation of the 2MLP-AC23
The 2MLP-AC23 delivers >65% efficiency. It accepts AC 170V to 264V and 47-63 Hz. This unit withstands 10 ms power interruptions.
Primary output is DC 5V ±2% at 8.5A. Overcurrent protection starts at 9.0A. Overvoltage protection triggers between 5.5V and 6.5V. These safeguards protect PLC modules.

The RUN contact supplies DC 24V at 0.5A. Mechanical life exceeds 20 million cycles. Electrical life reaches 100,000 operations at rated load. Response ON time is 10 ms or less; OFF time is 12 ms or less.
Buyer Guide and Procurement Alignment
Procurement engineers need matching voltage and current specs. This Honeywell 2MLP-AC23 directly fits MasterLogic-200 racks. Its built-in UL standard input fuse ensures safety. The fuse is not user-replaceable, so plan for spare units.
The unit weighs only 0.6 kg. It accepts cables from 0.75 mm to 2 mm. Use compressed terminals RAV 1.25-3.5 or RAV 2-3.5. A green LED indicates normal output voltage.
For harsh industrial lines, this module handles fluctuations. Order the 2MLP-AC23 for dependable DC power.

Logistics & Standard Packaging Details
- One Honeywell 2MLP-AC23 power module per package
- Product documentation and quick-start guide included

- Standard anti-static bubble wrap protection
- Express shipping available via FedEx, UPS, and DHL