TSXCANCA100: Schneider CANopen 100m Standard Cable Guide
Strategic Implementation of TSXCANCA100
Core Application Value
This 100-meter cable reel solves the challenge of maintaining signal stability over long distances in electrically noisy environments. Specifically, it excels in applications where Modicon M241, M251, or Premium controllers must synchronize with Lexium drives or Altivar VFDs. Engineers specify the Schneider Electric TSXCANCA100 because its high-coverage shielding minimizes the impact of electromagnetic interference (EMI). Therefore, the hardware ensures that critical "Heartbeat" and "PDO" (Process Data Object) messages are delivered without corruption. Furthermore, the 100m length provides flexibility for custom-length drops and trunk lines.

Technical Insights and Parameters
The hardware consists of a 4-wire assembly: one pair for data (CAN_H and CAN_L) and one pair for the optional auxiliary power supply (VP and VG). Moreover, the Schneider Electric TSXCANCA100 is color-coded according to the CANopen standard (Blue/White for data, Red/Black for power) to simplify wiring and reduce installation errors. Because the cable features a specialized PVC outer jacket, it resists the common oils and chemicals found in industrial settings. Thus, you ensure a long service life in factory floor conditions. Additionally, the cable's capacitance is strictly controlled to support baud rates up to 1 Mbps over shorter distances.
Robust Environmental Design
A multi-layer shielding architecture, including both foil and braid, protects the data pairs from high-frequency noise generated by nearby power cables. Moreover, the TSXCANCA100 is designed to maintain its electrical characteristics even when installed in standard cable trays or conduits. This durability facilitates long-term operation in automated warehouses and automotive assembly lines. Additionally, the cable is rated for static industrial installations where moderate mechanical stress is present. As a result, the system maintains a high Signal-to-Noise Ratio (SNR) across the entire 100-meter segment.

Field Installation and TSXCANCA100 Maintenance
Termination and Topology Integrity
Field experience indicates that missing or incorrect termination resistors represent the most common cause of "Bus Off" errors on a network using Schneider Electric TSXCANCA100. Therefore, you must verify that a 120-ohm resistor is installed at the two physical ends of the trunk line. Incorrect stripping of the shield can lead to ground loops if the drain wire is not properly bonded to the connector shell. When you utilize Schneider-certified CANopen connectors (such as the TSXCANKCDF series), technicians can ensure a tool-free, reliable connection. Furthermore, maintaining a minimum separation from high-voltage motor leads acts as a mechanical necessity for signal purity.
Diagnostics and Physical Layer Testing
Field technicians should utilize a digital multimeter or a CAN analyzer to check the resistance between CAN_H and CAN_L, which should measure approximately 60 ohms in a powered-down, terminated network. If the TSXCANCA100 shows signs of intermittent communication, you should inspect the jacket for abrasions or sharp bends that exceed the minimum bend radius. In addition, verifying that the shield is grounded at only one point (typically at the master PLC) ensures that stray currents do not interfere with the data signal. Finally, proper cable management in the cabinet protects the cable entry points from physical strain and insulation wear.
Buyer’s Guide and FAQ
Length: 100-meter (328 ft) reel.
Cable Type: Standard CANopen (2 pairs + shield).
Standards: UL certified, Flame retardant (IEC 60332-1).
Compatibility: Optimized for Schneider Electric CANopen tap junctions and connectors.
Authenticity: Always verify the "TSXCANCA100" part number and Schneider Electric branding on the cable jacket and reel. For more technical data, visit our [industrial product documentation center].